1. Steam boiler safety valves: Generally, open, full-lift spring safety valves (0490 series) are selected.
2. Safety valves for liquid media: Generally, low-lift spring safety valves (0485 series) are selected.
3. Safety valves for air or other gaseous media: Generally, full-lift spring safety valves are selected.
4. Safety valves for liquefied petroleum gas (LPG) tank trucks or LPG railway tank cars: Generally, full-lift internal safety valves are selected.
5. Safety valves for oil well outlets: Generally, pilot-operated safety valves are selected.
6. High-pressure bypass safety valves for steam power generation equipment: Generally, pilot-operated safety valves with both safety and control functions are selected.
7. If periodic opening tests of the safety valve are required, a safety valve with a lifting wrench should be selected. When the medium pressure reaches more than 75% of the opening pressure, the valve disc can be slightly lifted from the valve seat using the lifting wrench to check the flexibility of the safety valve's opening.
8. If the medium temperature is high, to reduce the temperature of the spring chamber, a safety valve with a radiator should generally be selected when the operating temperature of a closed safety valve exceeds 300℃ and the operating temperature of an open safety valve exceeds 350℃.
9. If the back pressure at the outlet of the safety valve fluctuates, and the change exceeds 10% of the opening pressure, a bellows safety valve should be selected.
10. If the medium is corrosive, a bellows safety valve should be selected to prevent critical components from failing due to corrosion.
11. The following points should be noted for the installation and maintenance of safety valves: 1) The installation position, height, and inlet/outlet direction must meet the design requirements. Ensure the direction of medium flow is consistent with the arrow direction marked on the valve body, and the connection should be firm and tight. 2) A visual inspection must be performed before valve installation. The valve nameplate should comply with the current national standard "General Valve Marking" GB 12220. For valves with an operating pressure greater than 1.0 MPa and those serving a shut-off function on main pipelines, strength and tightness tests must be conducted before installation. Only valves that pass these tests are permitted for use. During the strength test, the test pressure is 1.5 times the nominal pressure, and the duration is no less than 5 minutes. The valve body and packing should show no leakage to be considered合格 (qualified). During the tightness test, the test pressure is 1.1 times the nominal pressure; the test duration must comply with the requirements of GB 50243. All safety valves should be installed vertically.
12. There should be no resistance at the outlet of the safety valve to avoid pressure buildup.
13. Safety valves should be specifically tested and their sealing performance checked before installation.
14. Safety valves in use should be inspected periodically.